15/88 Operating

Manual

SG Series 10, 20, 30 & 40 kVA

3.3.2 Features of RPA parallel system

The

SG Series parallel system is designed to provide a complete Redundant Parallel

Architecture, and is free from common equipment.
Not only the Inverters are redundant, but also the Bypass functions are designed with
redundant modular concept.

When one UPS needs maintenance or service, the Load is powered by the other units
supplying the Load
bus.

The redundant communication bus to which all units are connected keeps each unit informed
about the status of all the other units.

The control panel located on each unit allows controlling and monitoring the status of this
unit.


3.3.3 System

control

A high-speed redundant, serial communication bus guarantees the exchange of data and
thus the communication between the CPU's of each unit.

Each module controls it's own function and operational status and communicates with all other
modules, in order to act or react if necessary, adapting it to the new conditions.


3.3.4 Synchronization

All units are identical, but one unit is arbitrarily selected as the reference and all the other units
synchronize to this unit, which in turn, synchronizes to the Utility Bypass voltage, as long as
the later is within tolerances.

In case of reference failure, another unit in the parallel system is automatically chosen to take
over the reference role.

The Bypass Input for all the units of the parallel system must be supplied from the same AC
source (no phase shift allowed between them).


3.3.5 Load sharing

On each unit of the parallel system, Inverter Output Voltage and Current are measured and
applied to a Load sharing bus.

An eventual difference between the units is therefore automatically equalized.

It is strongly recommended that no transformers, automatic circuit
breakers or fuses should be inserted between the unit’s output and the
Load
common bus bars.
However, it is recommended that a disconnect or isolation switch be
inserted.