84/88 Operating

Manual

SG Series 10, 20, 30 & 40 kVA

9.4

CONNECTION FOR OPTIONS

The installation and cabling of the options must be performed a qualified
service person.

9.4.1 Remote Signaling Box (RSB)

The optional Remote Signaling Box allows monitoring of the operation of the UPS, using the potential
free contacts fitted on the P4 - Customer Interface Board of the UPS.
It can be used by simply putting the box on a desktop or on a wall or, removing the box, it can be
surface mounted.
The remote panel contains an internal buzzer and the following status indicators:

Mimic diagram with

LED's indicating the operation of Rectifier and Inverter, and the power

source supplying the critical Load.

Alarm

(LED light and audible alarm) indicating a critical situation on the UPS.

Stop

indicating the UPS is preparing to shut down in a short time.

Mute

push button to reset the buzzer.

Test

push button checks all the LED’s and the buzzer of the remote panel.

The cable connecting the RSB to the UPS cabinet must be min. 16 wires / 0.25mm

2

.

The plug B is included in the delivery of the option RSB (cable connecting UPS with RSB not included).
Maximal admitted length: 985 ft (300 m).
It must be wired at one end with a D - female plug- 25 pin (J2 – P4 Customer Interface Board).

The alarms on free potential contacts can be connected on terminals X1
instead J2
(see correlation X1 – J2 in chapter 8.1).

Mute

Test

max 985ft /

300m

yellow/brown

white/yellow

1

2

4
3

5

brown/green

7
6

8

10
9

11

white/green

blue/red

violet

grey/pink

13
12

14

16
15

17

yellow

green

brown

20

22

23

19
18

21 white

24

16

COMMON ALLARM

AUX. BUZZER

STOP OPERATION

20
22
23

17
19

38

LOAD ON MAINS

LOAD ON INVERTER

56

55

50

43
44

49

40
42

SIGNALLING

UTILITY FAILURE

GND

24V

34

37

33

32

31

X15

IM6544

1
2

J2

-

SU

B D - MA

LE

REMOTE

X3

X4

A

A

B -

P4 - IM0005

B

PLUG

J2

77

m

m

3

in

130

mm

216mm

5 1/

4"

in

8 1/2" in

25

black

P.S.: The above mentioned colors are

XA

TERMINALS BLOCK

TERMINALS

XA

pin

k

red

bl

ue

gre

y

pink
red

grey
blue

SUB D - MALE

suitables only for XY standard cable

S

G

T

50

0

0_

O

P

T

_

01

0

-1

5

0_

R

M

S

_0

1U

S

1

12
13

2

14

3

15

4

16

5

17

6

18

7

19

8

20

9

21

10

22

11

1

14

9

1

2

1

1

2

3

4

1

2

3

4

J2

XA

BLOCK

BOX

Pink + Red

Grey + Blue

Stop

Alarm

g

GE Digital Energy

Customer Interface

2

1

Fig. 8.4.1-1 Remote Signaling Box connection

A Terminals

X3, X4 and X15 fitted inside the Remote Signaling Box.

B

Plug J2 (sub D - male - 25 pin) must be connected to the connector J2 (sub D - female-
25 pin) located on P4 - Customer Interface Board.

XA Terminals

block

XA for 24 VDC / 1A supply Remote Signaling Box.

If the remote signal panel is plugged on connector J2, the terminal blocks X1
cannot be used to drive an external alarms monitoring device, because it is
supplied by the internal UPS low voltage power supply.