GE SG SERIES 20 User Manual

Page 21

Advertising
background image

g

GE

OPM_SGS_USM_10K_40K_0US_V010.doc

21/88 Operating

Manual

SG Series 10, 20, 30 & 40 kVA

alarm

General alarm condition.
It blinks
when one or more alarm is activated. The internal buzzer is ON.
The LED remains lighted (with alarm condition still present) and the
buzzer stops as the key “mute” has been pressed.

service check

LED ON indicates that a regular maintenance service is needed.
May be reset by a service technician only.
(See chapter 10 – Maintenance)
THE LED IS ON ALSO WHEN THE OUTPUT SWITCH Q1 IS OPEN,
INDICATING THAT THE INVERTER
IS IN SERVICE MODE, NOT
SUPPLYING THE LOAD.

a) LED ON indicates that the Battery reserve lasts for only 3 more

minutes (selectable).

b) LED ON in case of over temperature or overload >125% together with

missing Utility.
After the timeout the Inverter
will shut down.

All LED’s ON indicate that the Battery is fully charged.
LED a
Yellow

(Fixed: indicating last 25 % of Battery backup)
(Blinking: indicating Battery backup

5%)

LED b, c, d Green

(EACH ONE INDICATING 25 % OF BATTERY BACKUP)

LED’s ON indicate the Load status of the UPS.
LED d
red (

100 % load)

LED c yellow

(100%

load)

LED b green

(66%

load)

LED a green

(33%

load)

Fig. 5.2.1-1 LED’s on synoptic diagram

Definition of the LED’s on mimic diagram
LED 1
= Input Utility Rectifier (green)
LED 2 = Input Utility Bypass (green)
LED 3 =

Rectifier

ON

(green)

LED 4a = Discharging (yellow)
LED 4b = Charging (green)
LED 5 = Inverter ON (green)
LED 6 = Load on Inverter (green)
LED 7 = Load on Utility (green)
LED 8 = Output Load Voltage (green)
LED 9 = Manual Bypass (Q2) ON (yellow)

Fig. 5.2.1-2 LCD screen

User LCD Interface
Consist of a LCD screen, 4 lines with 20
characters each and six keys. It offers:

UPS operating, AC and DC metering
information.

History of alarms and events.

Functionality can be programmed to meet
customer needs by changing parameters.