36/88 Operating

Manual

SG Series 10, 20, 30 & 40 kVA

Code

Alarms

Meaning

4115

LOW BATTERY

VOLTAGE

The Battery has been discharged and reached “stop
operation”
time-out (default 3 minutes), and the Inverter will
be shut down.
It will restart automatically only when the Battery has
recharged enough for a minimum runtime.

4116

HIGH BATTERY

VOLTAGE

Dangerous high DC Voltage caused inverter shutdown.
Inverter restarts automatically after Battery returns to floating
voltage.

4117

BATTERY

EARTH FAULT

A leakage current to earth has been detected on the DC
circuit.

4118

BATTERY FAULT

During battery test the voltage falls under the critical level
(depending setting parameters).
Battery test is stopped.

4130

TURN ON RECT.

OR SHUTDOWN UPS

Rectifier and Inverter are OFF.
The DC power supply is discharging the Battery.
Rectifier must be restarted or Battery must be disconnected in
order to avoid damage.

4140

RECTIFIER

CONTROL FAILURE

Rectifier Voltage hasn’t reached the set value (probably fault
on regulation loop). LED Rectifier on control panel is blinking.

4301

INVERTER

FUSES FAILURE

Inverter Output Fuses blown (F5, F6 and F7).
Inverter can be started manually after replacement of the
fuses.

4304

K7 CLOSING

FAILURE

K7 not closed despite a closing command being issued.
Signaled by auxiliary contact.
Load will be supplied by Utility.

4305

K7 OPENING

FAILURE

K7 not open despite an opening command being issued.
Signaled by auxiliary contact.
Load will be supplied by Utility.

4307

INVERTER

TRANSFORMER

OVERTEMPERATURE

The temperature sensor of the Inverter Transformer indicates
over temperature.
Elapsed “stop operation” time, Inverter shutdown.
With Utility OK, Load is transferred on Utility.

4308

DC FUSES

FAILURE

Blown input DC fuse(s) F1 of the Inverter.
Inverter cannot be started as long as present.

4309

DRIVER

FAILURE

An abnormal condition has been detected on one or more
power modules of the Inverter (temperature or over current).
Inverter shutdown and cannot be started as long as the alarm
is present.

4312

INV. VOLTAGE

OUT OF TOLERANCE

Inverter Output Voltage is out of the tolerances (

±

10%).

Inverter is switched OFF.

4320

ISMAX

DETECTION

Detection of Inverter Bridge (Is) current limit causing the
Inverter OFF and automatic re-start.
After 3 times the Inverter switches-Off, and it can be restarted
manually.

4340

INVERTER

CONTROL FAILURE

The “Slave” oscillator is not in synchronized with the Master;
thus causing the shutdown of it’s Inverter.
If after a restart the condition remains, the LED inside the
Inverter symbol on the panel will not light up, indicating that
this Inverter cannot supply the Load anymore.