23/88 Operating

Manual

SG Series 10, 20, 30 & 40 kVA

6.1 METERING

MODE

The metering mode is entered any time the metering button is pressed.
While in this mode the LCD will display a series of screens containing metering information.
In this mode the buttons perform the following functions:
metering

Scrolls forward to the next screen.

alarms Abandons

the

metering mode and enters the alarms mode.

parameters Abandons

the

metering mode and enters the parameters mode.

+

Scrolls forward to the next screen.

Scrolls backward to the previous screen.

ok

Displays the main screen for this mode.

Main screen
This screen displays the current status of the UPS in a condensed form.
The information offered by this screen consists of:

The type of the machine: Family name, series number (P + unit number for parallel
version from 1 to 8) and power range.

The status of the load.

The Load amount as a percentage of the nominal Load (referred to the most loaded phase).

The estimated Battery backup time in minutes with the present load.

SG Series S0 30kVA
LOAD ON INVERTER

LOAD = 84%

Autonomie = 12min

metering

alarms

parameters

+

ok

Battery data screen
This screen displays:

The Battery voltage.

The Battery Current (negative values correspond to the discharge of the Battery).

The temperature of the Battery (XXX indicates sensor disabled).

The current charge level.

The estimated backup time with the present load.

Ub=540V Ib= + 15A

Battery Temp= + 20

°

C

Charge Level= 87%
Autonomy = 12min

metering

alarms

parameters

+

ok

Bypass Utility data screen
This screen refers to the AC source supplying the Bypass. This screen displays:

The frequency.

The voltage levels of the three phase voltages.

U TILIT Y

f = 60.0 H z

U 1=2 76V U 2=27 5V

U 3= 277V

m eterin g

alarm s

pa ram eters

+

ok