58/88 Operating

Manual

SG Series 10, 20, 30 & 40 kVA

7.3.4 Separate a Unit from the parallel system (System Redundancy)

Initial status: Load supplied from all Inverters.

First operated unit

All other units of the system

1. Press and hold inverter off ( O ) key on the Unit to separate, until the LED

turns OFF.
Load
supplied from Inverter(s) of the other Unit(s) of the parallel system

.

First operated unit

All other units of the system

2. Open Q1 (Pos. O) and, only when the LED service check is ON, press total off

button on the Unit to separate.

First operated unit

All other units of the system

3. Disconnect the Battery, in case of External Battery, from the Unit to separate.

Wait 5 minutes for DC-Link Capacitors discharge.

4. Disconnect the Utility supply from the separated Unit.

First operated unit

All other units of the system

End of procedure

For any further intervention could nearest Service Center.