13 - 3

13. OPTIONS AND AUXILIARY EQUIPMENT

Subtract the capacitor charging from the result of multiplying the sum total of regenerative energies by
the inverse efficiency to calculate the energy consumed by the regenerative brake option.

ER [J]

Es Ec

Calculate the power consumption of the regenerative brake option on the basis of single-cycle operation
period tf [s] to select the necessary regenerative brake option.

PR [W] ER/tf............................................................................................(13.1)

(3) Connection of the regenerative brake option

Set parameter No.2 according to the open to be used.
The MR-RB65, 66 and 67 are regenerative brake options that have encased the GRZG400-2 ,
GRZG400-1 and GRZG400-0.8 , respectively. When using any of these regenerative brake options,
make the same parameter setting as when using the GRZG400-2 , GRZG400-1 or GRZG400-0.8
(supplied regenerative brake resistors or regenerative brake option is used with 11kW or more servo
amplifier).

Parameter No.0

Selection of regenerative
00: Regenerative brake option or regenerative brake option is not used
with 7kW or less servo amplifier
Supplied regenerative brake resistors or regenerative brake option is
used with 11kW or more servo amplifier
02: MR-RB032
03: MR-RB12
04: MR-RB32
05: MR-RB30
06: MR-RB50
08: MR-RB31
09: MR-RB51

by fans to increase capability

0E: When regenerative brake resistors supplied to 11kW or more are cooled