2 when alarm or warning has occurred, 1 alarms and warning list, Troubleshooting – MITSUBISHI ELECTRIC MELSERVO MR-J2S- A User Manual

Page 199

Advertising
background image

10 - 6

10. TROUBLESHOOTING

10.2 When alarm or warning has occurred

POINT

Configure up a circuit which will detect the trouble (ALM) and turn off the
servo-on (SON) at occurrence of an alarm.

10.2.1 Alarms and warning list

When a fault occurs during operation, the corresponding alarm or warning is displayed. If any alarm or
warning has occurred, refer to Section 10.2.2 or 10.2.3 and take the appropriate action. When an alarm
occurs, ALM turns off.
Set " 1" in parameter No. 49 to output the alarm code in ON/OFF status across the corresponding
pin and SG. Warnings (AL.92 to AL.EA) have no alarm codes. Any alarm code is output at occurrence of
the corresponding alarm. In the normal status, the signals available before alarm code setting (CN1B-19:
ZSP, CN1A-18: INP or SA, CN1A-19: RD) are output.
After its cause has been removed, the alarm can be deactivated in any of the methods marked in the
alarm deactivation column.

(Note 2) Alarm code

Alarm deactivation

Display

CN1B-19

pin

CN1A-18

pin

CN1A-19

pin

Name

Power

OFF

ON

Press

"SET" on

current

alarm

screen.

Alarm

reset

(RES)

AL.10

0

1

0

Undervoltage

AL.12

0

0

0

Memory error 1

AL.13

0

0

0

Clock error

AL.15

0

0

0

Memory error 2

AL.16

1

1

0

Encoder error 1

AL.17

0

0

0

Board error

AL.19

0

0

0

Memory error 3

AL.1A

1

1

0

Motor combination error

AL.20

1

1

0

Encoder error 2

AL.24

1

0

0

Main circuit error

AL.25

1

1

0

Absolute position erase

AL.30

0

0

1

Regenerative error

(Note 1)

(Note 1)

(Note 1)

AL.31

1

0

1

Overspeed

AL.32

1

0

0

Overcurrent

AL.33

0

0

1

Overvoltage

AL.35

1

0

1

Command pulse frequency error

AL.37

0

0

0

Parameter error

AL.45

0

1

1

Main circuit device overheat

(Note 1)

(Note 1)

(Note 1)

AL.46

0

1

1

Servo motor overheat

(Note 1)

(Note 1)

(Note 1)

AL.50

0

1

1

Overload 1

(Note 1)

(Note 1)

(Note 1)

AL.51

0

1

1

Overload 2

(Note 1)

(Note 1)

(Note 1)

AL.52

1

0

1

Error excessive

AL.8A

0

0

0

Serial communication time-out error

AL.8E

0

0

0

Serial communication error

Alar

m

s

88888

0

0

0

Watchdog

AL.92

Open battery cable warning

AL.96

Home position setting warning

AL.9F

Battery warning

AL.E0

Excessive regenerative warning

AL.E1

Overload warning

AL.E3

Absolute position counter warning

AL.E5

ABS time-out warning

AL.E6

Servo emergency stop warning

AL.E9

Main circuit off warning

Wa

rni

ngs

AL.EA

ABS servo-on warning

Removing the cause of occurrence
deactivates the alarm
automatically.

Note 1. Deactivate the alarm about 30 minutes of cooling time after removing the cause of occurrence.

2. 0: off

1: on