2 auxiliary equipment, 1 recommended wires, Options and auxiliary equipment – MITSUBISHI ELECTRIC MELSERVO MR-J2S- A User Manual

Page 264

Advertising
background image

13 - 39

13. OPTIONS AND AUXILIARY EQUIPMENT

13.2 Auxiliary equipment

Always use the devices indicated in this section or equivalent. To comply with the EN Standard or UL/C-
UL (CSA) Standard, use the products which conform to the corresponding standard.

13.2.1 Recommended wires

(1) Wires for power supply wiring

The following diagram shows the wires used for wiring. Use the wires given in this section or
equivalent.

C

P

U

V

W

L

11

L

21

B1

B2

U

V

W

L

1

L

2

L

3

Motor

Brake unit or
Return converter

N

1) Main circuit power supply lead

Power supply

Servo amplifier

3) Motor power supply lead

Servo motor

Electro-
magnetic
brake

Encoder

Encoder cable
(refer to Section 13.1.5)

4) Regenerative brake option lead

5) Electromagnetic
brake lead

2) Control power supply lead

Regenerative brake option

6) Brake unit lead or

Return converter

Cooling fan

BU

BV

BW

Fan lead

Power supply

The following table lists wire sizes. The wires used assume that they are 600V vinyl wires and the
wiring distance is 30m(98.4ft) max. If the wiring distance is over 30m(98.4ft), choose the wire size in
consideration of voltage drop.
The alphabets (a, b, c) in the table correspond to the crimping terminals (Table 13.2) used to wire the
servo amplifier. For connection with the terminal block TE2 of the MR-J2S-100A or less, refer to
Section 3.11.
The servo motor side connection method depends on the type and capacity of the servo motor. Refer to
Section 3.8.
To comply with the UL/C-UL (CSA) Standard, use UL-recognized copper wires rated at 60 (140 ) or
more for wiring.

Advertising