13. OPTIONS AND AUXILIARY EQUIPMENT

13.2.5 Relays

The following relays should be used with the interfaces:

Interface

Selection example

Relay used for digital input command signals (interface
DI-1)

To prevent defective contacts , use a relay for small signal
(twin contacts).
(Ex.) Omron : type G2A , MY

Relay used for digital output signals (interface DO-1)

Small relay with 12VDC or 24VDC of 40mA or less
(Ex.) Omron : type MY

13.2.6 Surge absorbers

A surge absorber is required for the electromagnetic brake. Use the following surge absorber or equivalent.

Insulate the wiring as shown in the diagram.

Maximum rating

Permissible circuit

voltage

Surge

immunity

Energy

immunity

Rated

power

Maximum

limit voltage

Static

capacity

(reference

value)

Varistor voltage

rating (range) V1mA

AC[Vma] DC[V]

[A]

[J]

[W]

[A]

[V]

[pF]

[V]

140

180

(Note)

500/time

5

0.4

25

360

300

220

(198 to 242)

Note. 1 time 8

20 s

(Example) ERZV10D221 (Matsushita Electric Industry)
TNR-10V221K (Nippon chemi-con)
Outline drawing [mm] ( [in] ) (ERZ-C10DK221)

13.5 (0.53)

16.

5

(0.6

5)

3.

0 (0.

1

2

)

or l

e

ss

30.

0

(1.

1

8)

or m

o

re

Crimping terminal
for M4 screw

Vinyl tube

4.7 1.0 (0.19 0.04)

0.8 (0.03)

13.2.7 Noise reduction techniques

Noises are classified into external noises which enter the servo amplifier to cause it to malfunction and
those radiated by the servo amplifier to cause peripheral devices to malfunction. Since the servo amplifier
is an electronic device which handles small signals, the following general noise reduction techniques are
required.
Also, the servo amplifier can be a source of noise as its outputs are chopped by high carrier frequencies. If
peripheral devices malfunction due to noises produced by the servo amplifier, noise suppression measures
must be taken. The measures will vary slightly with the routes of noise transmission.
(1) Noise reduction techniques

(a) General reduction techniques

Avoid laying power lines (input and output cables) and signal cables side by side or do not bundle

them together. Separate power lines from signal cables.

Use shielded, twisted pair cables for connection with the encoder and for control signal

transmission, and connect the shield to the SD terminal.

Ground the servo amplifier, servo motor, etc. together at one point (refer to Section 3.10).