8 leakage current breaker, Options and auxiliary equipment – MITSUBISHI ELECTRIC MELSERVO MR-J2S- A User Manual

Page 275

Advertising
background image

13 - 50

13. OPTIONS AND AUXILIARY EQUIPMENT

13.2.8 Leakage current breaker

(1) Selection method

High-frequency chopper currents controlled by pulse width modulation flow in the AC servo circuits.
Leakage currents containing harmonic contents are larger than those of the motor which is run with a
commercial power supply.
Select a leakage current breaker according to the following formula, and ground the servo amplifier,
servo motor, etc. securely.
Make the input and output cables as short as possible, and also make the grounding cable as long as
possible (about 30cm (11.8 in)) to minimize leakage currents.

Rated sensitivity current 10 {Ig1 Ign Iga K (Ig2 Igm)} [mA] ..........(13.2)

K: Constant considering the harmonic contents

Leakage current breaker

Type

Mitsubishi

products

K

Models provided with
harmonic and surge
reduction techniques

NV-SP

NV-SW

NV-CP

NV-CW

NV-L

1

General models

BV-C1

NFB

NV-L

3

M

Servo

amplifier

Noise

filter

NV

Ig1 Ign

Iga

Ig2

Igm

Cable

Cable

Ig1:

Leakage current on the electric channel from the leakage current breaker to the input terminals
of the servo amplifier (Found from Fig. 13.1.)

Ig2:

Leakage current on the electric channel from the output terminals of the servo amplifier to the
servo motor (Found from Fig. 13.1.)

Ign:

Leakage current when a filter is connected to the input side (4.4mA per one FR-BIF)

Iga:

Leakage current of the servo amplifier (Found from Table 13.6.)

Igm:

Leakage current of the servo motor (Found from Table 13.5.)

Table 13.5 Servo motor's

leakage current
example (Igm)

Table 13.6 Servo amplifier's

leakage current

example (Iga)

Servo motor

output [kW]

Leakage

current [mA]

Servo amplifier

capacity [kW]

Leakage

current [mA]

0.05 to 0.5

0.1

0.1 to 0.6

0.1

0.6 to 1.0

0.1

0.7 to 3.5

0.15

1.2 to 2.2

0.2

5 7

2

3 to 3.5

0.3

11 15

5.5

5

0.5

22

7

7

0.7

Table 13.7 Leakage circuit breaker selection example

11

1.0

15

1.3

22

2.3

Servo amplifier

Rated sensitivity

current of leakage

circuit breaker [mA]

MR-J2S-10A to MR-J2S-350A
MR-J2S-10A1 to MR-J2S-40A1

15

MR-J2S-500A

30

MR-J2S-700A

50

120

100

80

60

40

20

0

2 3.5

5.5

8 1422 38 80 150

30 60 100

Fig. 13.1 Leakage current example
(Ig1, Ig2) for CV cable run
in metal conduit

Cable size[mm

2

]

[mA]

Le

a

k

ag

e

cu

rr

e

n

t

MR-J2S-11KA to MR-J2S-22KA

100

Advertising