14. COMMUNICATION FUNCTIONS

14.12.6 External input signal ON/OFF (test operation)

Each input signal can be turned on/off for test operation. Turn off the external input signals.
Send command [9] [2], data No. [0] [0] and data.

Command

Data No.

Set data

[9][2]

[0][0]

See below

b31

b0

0: OFF

1: ON

b1

Command of each bit is transmitted to the slave
station as hexadecimal data.

bit

Signal abbreviation

bit

Signal abbreviation

bit

Signal abbreviation

bit

Signal abbreviation

0

SON

8

16

24

1

LSP

9

17

25

2

LSN

10

18

26

3

TL

11

ST1

19

27

4

12

ST2

20

28

5

PC

13

21

29

6

RES

14

22

30

7

CR

15

23

31