MITSUBISHI ELECTRIC G-50A User Manual

Page 23

Advertising
background image

-21-

Press the switch to display the group in desired weekly

Press the switch to move the cursor to the pat-

tern position to be set.

schedule setting.

• Setting the set-back values and setting temperature can be performed only when selecting either "SET BACK"

• Set-back operation

• Cooling operation : 24˚C+2˚C=26˚C / 75˚F+4˚F=79˚F
• Heating operation : 24˚C-2˚C=22˚C / 75˚F-4˚F=71˚F

• Setting temperature operation

This operation sets the temperature when timer ON is set to a predesignated temperature regardless of the op-
eration mode.

Press the

Press the

/

(CLOCK/PATTERN) switch to
select the following items.

• Set-back value;

The reference temperature and

• Setting temperature:

The setting temperature for
each ON time period is selected.

Press the switch to make

setting.

Repeat operations and to

set the set-back value or setting
temperature for each ON/OFF
schedule.

Press the switch, when finis-

* The selecting range:

• The reference temperature for set-back operation

• The set-back value

• The setting temperature

The schedule pattern P1 to P3, local remote control prohibition (P4),

P1

to

P3

of a composite pattern composed of

P1 to P3 and P4, and non-timer operation(-) are set for each day.

: 19˚C 28˚C (1˚C unit) / 67˚F 83˚F (2˚F unit)

: 19˚C 28˚C (1˚C unit) / 67˚F 83˚F (2˚F unit)

: 0 9 degree (1 degree unit)
/ 0 18 degree (2 degree unit)

set-back value for each ON time
period are selected.

switch to move the cursor posi-
tion to the set-back reference
temperature or setting tempera-
ture.

Set-back operation is a method which reduces the air conditioner running cost by controlling the operation with
specified time band for lowered load. In other words the unit operates at a few degrees higher for cooling and
a few degrees lower for heating in the specified time band.

When the reference temperature is 24˚C / 75˚F and the set-back value is set to 2˚C / 4˚F.

EXAMPLE

or "SET TEMP" on the user setting screen in the initial setting mode.

(2) Set-back values and setting temperature setting

(3) Weekly schedule setting

hed.

NOTE: The temperature display

can be switched between
Celsius (

°C) or Fahrenheit

(

°F) (page 34).

5

8

GROUP
SELECT

BACK
SCREEN

ENTER

1

2

2

3

3

4

5

1

2

Advertising