Functions 3-1 specifications – MITSUBISHI ELECTRIC G-50A User Manual

Page 6

Advertising
background image

-4-

Cool (Dry) operation : 19 30 ˚C / 67 87 ˚F

Heat operation : 17 28 ˚C / 63 83 ˚F

Auto operation : 19 28 ˚C / 67 83 ˚F

DC24V,0.02A(Maximum loading)
Power received from PAC-SC50KUA Power Supply Unit via M-NET transmission line.
DC12V,0.2A(Maximum loading)
Power is received from the PAC-SC50KUA Power Supply Unit via the DC power line.

Indoor unit or independent OA processing unit or LOSSNAY

: 50 units maximum (50 groups maximum)

Number of units (indoor or independent OA processing unit or LOSSNAY) in one group

: 1-16 units

*Note

register to the same group.

Indoor unit, independent OA processing unit and LOSSNAY can not

Number of remote controllers in one group

Number of system controllers in one group

Number of indoor units interlocked with one OA processing unit or LOSSNAY

: 1-2

: 0-4 (including the number of remote controller in one group)
: 0-3 for groups which have one remote controller.

: 0-16 (some types of OA processing unit can only be operated when inter-

locked to a maximum of 9 units)

3

. Functions

3-1 Specifications

Item

Source power requirement

Environmental condition

Temperature

Humidity

120(H) 300(W) 80[*19](D)

4-3/4(H) 11-13/16(W) 3-1/8[*3/4](D)

1.0

2-1/4

Kg

lb

mm

in

Dimensions

Weight

System condition

Number of control unit

User operating function

Operation

Fan speed

Air direction
and swing
operation

Temperature
setting

ON/OFF

Operation
mode

*1

*3

*1

*1

The ON/OFF operation can be performed as a collective or per group.

The switch operation for the operation mode setting can be performed as a collective
or per group.

[ Selectable operation mode for the indoor unit ]

[ Selectable operation mode for the independent ventilation ]

Cool/Dry/Fan/Auto/Heat

Heat recovery/By-pass/Auto

The switch operation to set the High and Low speed can be performed as a collective
or per group.

( The 4 fan speed setting is available to the indoor that has 4 levels )

The air flow direction can be switched to 4 directions and swing operation as a collec-
tive or per group

Temperature setting can be performed collectively or per group.

[Setting temperature range]

Operating
Non operating

0 ˚C +40 ˚C / 32 ˚F +104 ˚F

-20 ˚C +60 ˚C / – 4 ˚F +140 ˚F

30 90%RH (No condensation)

Input voltage

Specification

*[ ] : indicate the thickness from the

wall.