5 - 5 interlocked operation setting – MITSUBISHI ELECTRIC G-50A User Manual

Page 31

Advertising
background image

-29-

5 - 5 Interlocked operation setting

• Registration of interlocked operation of Ventilation unit (OA processing unit and LOSSNAY) with single or multiple

indoor unit is performed. All indoor units to be interlocked with ventilation unit for operation should be registered

for the interlocking with ventilation unit.

<Example for the interlocked group configuration>

M-NET local remote controller

Outdoor unit

Indoor unit

OA processing unit or LOSSNAY

M-NET
Transmission line

Initial setting menu screen is displayed.

Press the switch to select "2 INTERLOCKED SETTING" .

The interlocked setting screen is displayed.

Minimum address of the interlocked OA processing unit or LOSSNAY unit

which can be set to interlock with indoor unit is displayed on the "INTERL-
OCKED UNIT ADDRESS" display position. And the cursor is displayed in
the unit address display position.

Press the switch to display the address number of the in-

terlocked OA processor unit or LOSSNAY that the setting will be perf-

NOTE:

Simultaneously press the and keys on the user operation menu
screen for 2 seconds.

Always perform the mode change operation from the user oper-
ation menu.
Mode change operation from other screens is ineffective even if
performed.

omed on.

NEXT

2

GROUP
SELECT

1

2

3

4

5