Re-configuring the double-axis motor module from 3A/3A to 5A/5A

This application example is configured as standard using a 3A/3A motor
module. However, there are demonstration cases in the field, which are still
equipped with a 5A/5A motor module. The hardware should be carefully
checked before the project is downloaded! If a 3A/3A motor module is not
used in the demonstration case, then the project can be re-configured by
following the subsequent instructions:

• Go

offline

• In the project tree, open the “Drive Navigator”
• A selection window opens when the “Device configuration” button is

pressed

• Open the Configurator by pressing the “Execute drive configuration"

button

• Scroll in the selection menu of the power unit by pressing the

“Continue” button

• Select the power unit being used from the list – refer to the serial

number on the front of the double motor module, e.g. 6SL3120-2TE15-
0AA0 (5A/5A)

• Press “Continue” and acknowledge the alarm messages
• Press the “Continue” button – without making any additional changes –

until the “Complete” button appears; also press this

• Close the Device Configurator
• In the Expert list of the red and blue drives (select the particular drive ->

righthand mouse key -> Expert -> Expert list), reduce parameter p210
from 600V to 345V

• Compile and save the project, go online and load the project into the

target system