6 delayed out door tem pe ra ture adap ta tion 44, Sum mer mode 44, Delayed outdoor temperature adaptation – Samson Trovis 5100 User Manual

Page 44: Outdoor temperature-dependent advance heating, 3 ot activation value in rated operation, 4 summer mode

Advertising
background image

When the outdoor temperature falls below this value (less 0.5 °C hysteresis), heating operation is
restarted immediately.

With the default settings, this means that, at night, the system is switched off at an outdoor tem-
perature of 10 °C to save energy. Nevertheless, remember that the system requires some time in
the morning to heat up the building (–> Outdoor temperature-dependent advance heating,
section 5.7).

Parameter

WE

Parameter level / Range of values

OT deactivation value
in reduced operation

10 °C

PA1, 2, 3 / –10 to 50 °C

5.5.3 OT activation value in rated operation

If a heating circuit is in reduced operation (automatic mode), the circuit is automatically trans-
ferred to rated operation when the outdoor temperature falls below the limit

OT activation value

in rated operation. When the limit value is exceeded (plus 0.5 °C hysteresis), reduced operation
is restarted.

This function is activated at very low temperatures to avoid the building cooling down exces-
sively outside the times-of-use when low outdoor temperatures occur.

Parameter

WE

Parameter level / Range of values

OT activation value
in rated operation

–15 °C PA1, 2, 3 / –30 to 50 °C

5.5.4 Summer mode

Summer mode is activated depending on the mean daytime temperature (measured between
7.00h and 22.00h) during the desired period.
If the mean daytime temperature exceeds the

Outdoor temperature limit in summer mode on

two consecutive days, summer mode is activated on the following day: the heating is switched
off. If the mean daytime temperature remains below the

Outdoor temperature limit in summer

mode on the next day, summer mode is deactivated on the following day.

Functions

WE

Configuration

Summer mode

OFF
01.06
30.09
18 °C

Co1, 2, 3 -> Fb11 = ON
Start summer mode / 01.01 (1 Jan) to 31.12 (31 Dec)
Stop summer mode / 01.01 to 31.12
Outdoor temperature limit in summer mode / 0 to 30 °C

44

EB 5179 EN

Functions of the heating circuit