Servicing should only be performed by a Qualified Service Agent

ccb connection identification
J1 Socket - Transformer

pin #

description

1

120 VAC hot to transformer

2

not used

3

120 VAC neutral to transformer

4

24 VAC out from transformer

5

24 VAC out from transformer

J2 Socket - 120 VAC To Combustion Blower

pin #

description

1

120 VAC hot to Combustion Blower 3 pin socket, see Figure 7 on page 11

2

120 VAC neutral to Combustion Blower 3 pin socket, see Figure 7 on page 11

3

not used

4

not used

J3 Socket - 120 VAC Power Supply

pin #

description

1

120 VAC hot

2

Earth Ground

3

120 vAC neutral

J4 Male Spade Connector - Flame Sensor
J5 Socket - Igniter 120 VAC HSI (hot surface igniter)

pin #

description

1

120 VAC hot

2

120 vAC neutral

J6 Socket - 24 Volt Gas Valve, Pressure Switches, Enable/Disable Circuit

pin #

description

1

not used

2

Gas valve - 24 VAC output (rectified to 24 VdC at the gas valve wiring harness plug end)

3

not used

4

Blocked Intake Air switch

5

Blocked Exhaust switch

6

Blower Prover switch

7

Blower Prover switch

8

Enable/disable external control circuit - jumper installed from factory

9

not used

10

Blocked Exhaust switch

11

Enable/disable external control circuit - jumper installed from factory

12

not used

13

not used

14

Blocked Intake Air switch

15

Gas valve - 24 VAC output (rectified to 24 VdC at the gas valve wiring harness plug end)