Flame sensor short, Flame detect error, Flame sensor short flame detect error – State Industries SHE50-100PE User Manual

Page 61: Fault messages

Advertising
background image

59

Servicing should only be performed by a Qualified Service Agent

fault messages

displayed message/condition/indicates

possible causes - checK/repair

Flame Sensor Short

The Control System has detected the Flame Sensor is

grounded.

CHANGE

BACK

ADVANCED

Flame Sensor Short

Fault occurred 2 mins ago

The flame sensor is grounded.

Call a service professional:

Your Company Name Here

(press [DOWN] for more....)

• Check all wiring and plugs between the J4 spade

connector on the CCB (page 41) and the Burner

Adapter wiring harness behind the CCB enclosure.

Ensure no wiring is pinched/shorted. Ensure no bare

wiring is touching any grounded surface. Repair/

replace anything worn or damaged.

• Remove the Combustion Blower and Burner

Assembly to inspect the Flame Sensor and the

Burner Adapter wiring harness. See Combustion

Blower and Burner Removal on page 14.
Ensure the Flame Sensor is not damaged or touching

the Burner. There should be a 1/2 inch gap between

the Flame Sensor and the Burner. See Flame Sensor

on page 18. Replace the Flame sensor and/or Burner

Adapter wiring harness if worn or damaged. Adjust

gap between the Flame Sensor and the Burner.

• Call the toll free support phone number on the back

cover of this manual for further assistance if the

problem has not been corrected after performing the

procedures outlined here.

Flame Detect Error

The Control System has detected flame sensing current

out of sequence.

CHANGE

BACK

ADVANCED

Flame Detect Error

Fault occurred 2 mins ago

Flame detected out of sequence.

Call a service professional:

Your Company Name Here

(press [DOWN] for more....)

Important Service Reminder:

When performing any troubleshooting steps outlined in

this manual always consider the wiring and connectors

between components. Perform a close visual inspection

of all wiring and connectors to a given component before

replacement.

• The Burner has not shut down properly. Check 24

Volt Gas Valve for 100% closure. Check for flame

candling after the heating cycle has ended through

the Burner Sight Glass. See Figure 4 on page 9 to

locate the Burner Sight Glass.

• If burner flame is candling after the heating cycle has

ended - replace 24 Volt Gas Valve. See Gas Valve

Removal on page 24.

• Call the toll free support phone number on the back

cover of this manual for further assistance if the

problem has not been corrected after performing the

procedures outlined here.