Temperatures, See temperatures – State Industries SHE50-100PE User Manual

Page 51

Advertising
background image

49

Servicing should only be performed by a Qualified Service Agent

temperatures
operating Set Point And Differential Adjustment
The operating Set Point is adjustable from 90°F (42°C) to 180°F (82°C) for commercial and 160°F (71°C)

on residential models. The factory setting is 120°F (49°C). The differential is adjustable from 2° to 20°.

The factory setting is 8°. When the water temperature sensed by the Control System from the Temperature

Probe reaches the operating Set Point the Control System will end the heating cycle. A heating cycle will be

activated again when the water temperature drops below operating Set Point minus the differential setting.
note: Set the operating Set Point to the lowest setting which produces an acceptable hot water supply for

the most efficient use. Lower differential settings may cause excessive heating cycles (short-cycling) which

can cause premature failure of components such as the Igniter. Set the differential at the highest setting

which produces an acceptable hot water supply to prevent short cycling.

description/action

display

From the desktop Screen, press the operational Button under

MEnu. The "Main Menu" screen will be displayed.

Tank Temperature

120°F

Operating Set Point

120°F

Status: Standby

MENU

HELP

MANUFACTURER / MODEL INFORMATION

The Main Menu is where all Control System menus are listed,

see Table 7 on page 48 for a complete list and description of

Control System menus. use the up and down Buttons to view

all Control System menus from the Main Menu.

With Temperatures menu selected (highlighted in black) in

the Main Menu screen, press the operational Button under

“SELECT” to enter the Temperatures menu.

If the Temperatures menu is not selected use the up and down

Buttons to select this menu item.

Temperatures

Heater Status

Display Settings

Heater Information

Current Fault

SELECT

BACK

HELP

Main Menu

With the operating Set Point selected in the Temperatures

menu, press the operational Button underneath “CHAnGE” to

activate the adjustment mode for this menu item.

If operating Set Point is not selected use the up and down

Buttons to select this menu item.

note: Higher Temperature settings increase wear and

operating costs. Set the operating Set Point to the lowest

setting which produces an acceptable hot water supply. This

will always provide the most energy efficient operation and

longer life.

Operating Set Point

120°F

Differential

8°F

Tank Temperature

120°F

Tank Probe Offset 0°F

CHANGE

BACK

HELP

Temperatures

With the adjustment mode for the operating Set Point activated

the selection bar will change from a black fill to a black outline.

use the up and down Buttons to change the current setting.

Press the operational Button under "uPdATE" to save the

new setting. Press the operational Button under "CAnCEL" to

discard changes and return to the previously saved setting.

note: use this same procedure to change the differential

setting and other adjustable user settings in the Control System

menus.

Operating Set Point

140°F

Differential

8°F

Tank Temperature

120°F

Tank Probe Offset

0°F

UPDATE

CANCEL

Temperatures

Advertising
This manual is related to the following products: