Blocked exhaust, Blower prover failure, Blocked exhaust blower prover failure – State Industries SHE50-100PE User Manual

Page 64: Fault messages

Advertising
background image

62

Servicing should only be performed by a Qualified Service Agent

fault messages

displayed message/condition/indicates

possible causes - checK/repair

Blocked Exhaust

The control system has detected the Blocked Exhaust

switch has open contacts - restricted/blocked vent piping,

the water heater is not venting properly.

CHANGE

BACK

ADVANCED

Blocked Exhaust

Fault occurred 2 mins ago

The exhaust is blocked or

restricted. Ensure

condensate hose is draining.

Call a service professional:

Your Company Name Here

(press [DOWN] for more....)

Important Service Reminder:

When performing any troubleshooting steps outlined in

this manual always consider the wiring and connectors

between components. Perform a close visual inspection

of all wiring and connectors to a given component before

replacement.

• Check the condensate drain on the water heater's

Exhaust Elbow, see Figure 3 on page 8 for location.

Water build up in the Exhaust Elbow will restrict the

venting system and cause this failure. Clear the

condensate drain line and ensure it is flowing freely.

• Check for restrictions - vent pipe size too small, too

many equivalent feet, or too many installed elbows

in the vent piping. Review venting installation section

of the Instruction Manual that came with the water

heater - see Table 1 on page 4 in this manual. Ensure

the vent/intake air piping has been installed within

manufacturers requirements.

• Ensure there is not a low point in the vent piping that

will allow water/condensate to collect and block the

vent piping.

• Check all wiring between the Blocked Exhaust

switch and the CCB’s J6 Socket (page 41) pins 5 &

10. Perform close visual inspection of the pins inside

the plug and socket - ensure plugs and sockets are

mating properly and providing good contact. Repair/

replace anything worn or damaged.

Perform the Pressure Switch Tests on page 31.

Replace the Blocked Exhaust switch if it is defective.

• Call the toll free support phone number on the back

cover of this manual for further assistance if the

problem has not been corrected after performing the

procedures outlined here.

Blower Prover Failure

The control system has detected the Blower Prover

switch has closed contacts out of sequence; before

the Combustion Blower has been energized. See the

Sequence of operation on page 54 and the Sequence of

operation Flow Chart on page 55.

CHANGE

BACK

ADVANCED

Blower Prover Failure

Fault occurred 2 mins ago

The blower prover switch is

closed out of sequence.

Call a service professional:

Your Company Name Here

(press [DOWN] for more....)

• Check all wiring between the Blower Prover switch

and the CCB’s J6 Socket (page 41) pins 6 & 7. Ensure

there are no shorted or pinched wires.

• Ensure there are no jumper wires installed on the

Blower Prover switch.

• Ensure there are no jumper wires installed between

the CCB’s J6 Socket pins 6 & 7.

Perform the Pressure Switch Tests on page 31.

Replace the Blower Prover switch if it is defective.

• Call the toll free support phone number on the back

cover of this manual for further assistance if the

problem has not been corrected after performing the

procedures outlined here.