INSTALLATION

A-3

A-3

IDEALARC R3R

TECHNICAL SPECIFICATIONS - IDEALARC R3R-400

INPUT - THREE PHASE ONLY

Standard Voltage

Input Current @ Rated Output

230V

74A

460V

37A

RATED OUTPUT

Duty Cycle

Amps

Volts at Rated Amps

100%

300

32

60%

400

36

35%

500

40

OUTPUT

Current Range

Maximum Open Circuit Voltage

60 to 500 Amps

67 VDC

RECOMMENDED INPUT WIRE AND FUSE SIZES AT 60% DUTY CYCLE

Input Wire Size

Ground Wire Size

Input Voltage /

Fuse

Input Ampere

Type 75°C

Type 75°C

Frequency

(Super Lag)

Rating on

Copper Wire in

Copper Ground

or Breaker Size

Nameplate

Conduit

Wire in Conduit

Volts/Hz

AWG (IEC) Sizes

AWG (IEC) Sizes

230/60

125

74

6 (16 mm

2

)

6 (16 mm

2

)

460/60

60

37

10 (6 mm

2

)

10 (6 mm

2

)

PHYSICAL DIMENSIONS

Height

Width

Depth

Weight

27.50 in.

22.25 in.

33.10 in.

402 lbs.

(700 mm)

(565 mm)

(840 mm)

(182 kg)