Configuration, Sensor template (factory default), Specifications – Phonetics IMS-4000 User Manual

Page 113

Advertising
background image

Configuration

All IMS Solution sensors are auto-configured when you plug them into the Host or Node. When a

new sensor is plugged into the Host or Node, the configuration is set to the factory default via the

Sensor Template.

If you have modified these templates, the configuration will be set to the modi-

fied configuration. When a sensor is removed, or the connection is disrupted, the configuration

data remains intact but the sensor will go into trouble status and generate a trouble alarm. When

the sensor is plugged in again, or the connection is re-established, configuration data remains

unchanged and the sensor returns to normal operating condition.

Caution

: Removing a sensor for less than 60 seconds does not produce a trouble alarm.

Removing or unplugging a sensor for more than 60 seconds or plugging in a different

sensor at any time will cause a trouble alarm.

Sensor Template (factory default)

Input Name: Temperature

Low Temperature Limit: 50º F

High Temperature Limit: 85º F

Recognition Time: 60 Seconds

Reset Time: 0 Seconds

Data Logging: Active

Voice: temperature.wav

Input Class: Temperature

Specifications

Range: 32–95 degrees F

Humidity: 5–90 %RH

Sensor type: solid state ic

Accuracy: +/- 3 degrees F

Connector: RJ-45

Housing: white plastic

113