Sample status report, Voice alarm dialout – Phonetics IMS-4000 User Manual

Page 88

Advertising
background image

IMS-4000 Manual

88

Sample Status Report

To receive a status report, call the unit. When it answers wait for the beep. Immediately after hear-
ing the beep, press any touch-tone. The unit will begin speaking and request your User Code. If the
unit receives a valid User Code it will continue with several menu options. A sample of the main
menu is shown below:

“Hello, this is the IMS-4000 at the IT Dept of XYZ Company
“Enter your user code:”
To hear the environmental status, press

1.

To hear the IP status, press

2.

To ping an IP device press

3.

To check the status of a PowerGate outlet, press

4.

To switch an outlet on a PowerGate, press

5.

To turn on the microphone, press

6.

To disconnect, press

7.

To repeat this menu, press

8.

If the caller had selected option 1 they would get a sub-menu asking if they would like to hear an
environmental alarm summary report or a full environmental status report. The alarm summary
only reports on inputs that are currently beyond their limits, or are in an alarm condition and have
a class match. The full report provides status on

all inputs that have a class match. A sample of a

full environmental status report is listed below. Items in italics are custom messages recorded by the
user.

Environmental sensors at the IT Dept of XYZ Company

Channel 1, temperature in the server room, is 76.4 degrees Fahrenheit, OK
Channel 2, temperature in rack B, is 82.7 degrees Fahrenheit, too high
Channel 3, humidity in the server room, is 33.9%, OK
Channel 6, water under server room floor, OK
Channel 7, smoke alarm in the server room, OK
Channel 9, battery, is 100.0%, OK
Channel 10, power, is 116.3 volts, OK
Channel 11, Sound level, OK

Note: The Voice menus are intelligent, such that they will only recite menu options if there is
relevant content. For example, if there are no IP Alarms programmed then the IP Alarm menu
option will be skipped, or if there is no PowerGate connected, then this menu option will be
skipped; or if the User has no Environmental sensors in his class, then these will be skipped.

Voice Alarm Dialout

The IMS-4000 can call and deliver an alarm message in spoken English. After dialing, the unit
will begin speaking “IMS-4000 Alarm Message, Press any key to continue.” If the unit receives a
touch-tone, it will recite the alarm message. When it finishes speaking the message it will request
acknowledgement (if the call type is Until Acknowledged; if the call type is Inform, the unit will
just speak the alarm message and disconnect). A sample Voice Alarm call is shown below:

Advertising