background image

!

Caution

: Removing a sensor for less than 60 seconds does not produce a trouble alarm.

Removing or unplugging a sensor for more than 60 seconds or plugging in a different

sensor at any time will cause a trouble alarm.

Host and Node Firmware Requirements

The 4-20mA Bridge requires the following firmware versions in the Host and Node(s) for sensor

compatibility:

IMS-4000 Host

• Input board firmware chip version xx.xx.xx.103 or higher
NOTE: Input board firmware is NOT flash upgradeable. A new firmware chip must be

installed. For information on obtaining a new firmware chip, please contact Sensaphone

Technical Support at 610.558.2700 or via e-mail at [email protected].

• ConsoleView version 2.04 or higher
• IMS4K OS version 2.41 or higher
• Voice version 2.09 or higher

*Host version information is viewable through the ConsoleView software on the Version Info

screen and the Help>About selection from the main menu.
IMS-4000 Node

• Firmware version 2.19 or higher.

*Node version information is viewable through the ConsoleView software on the Node

Properties>Diagnostics

screen.

Sensor Template (factory default)

Input Name: Transducer

Recognition Time: 3 Seconds

Reset Time: 0 Seconds

Data Logging: Active

Voice: None

Input Class: Other

Specifications

Input: 4–20mA DC

Current Limit: 50mA

Input Impedance: Variable (1000Ω @ 4mA, 260Ω @ 20mA)

Accuracy: ± 0.25%

IMS Connection: RJ-45

Operating Temperature Range: 32–122 deg F (0–50 degC)

Housing: Black plastic with mounting ears