Installing the New Water Heater (cont'd)

VENTING SYSTEM EXAMPLE INSTALLATIONS FOR

ALL MODELS

The vent piping cannot under any circumstances be run

downhill.

The vent piping can be installed as follows:

1. Horizontal runs require a minimum

1

/

8

″ rise per five feet.

3 ELBOW

EXAMPLE

MIN. RISE

1

8

PER FIVE FEET

MIN. RISE

1

8

PER FIVE FEET

3 ELBOW

EXAMPLE

*NOTE: Two 45˚ elbows are equivalent to one 90° elbow.

One 90˚ elbow equals 5 feet of equivalent vent length.

MIN. RISE

1

8

PER FIVE FEET

13

1

4

MIN.

11

1

4

MIN.

45

MAX.

18

MIN.

ONE ELBOW

MIN. RISE

1

8

PER FIVE FEET

MIN. RISE

1

8

PER FIVE FEET

MIN. RISE

1

8

PER FIVE FEET

CAULK

JOINT

3 ELBOW

EXAMPLE

2. The total vertical and horizontal vent runs cannot exceed

the maximum length with the number of 90˚ elbows as
specified in the table below. If more elbows are required,
the venting distance must be reduced 5 feet for every 90°
elbow:

3

″ DIA. VENTS

NUMBER OF 90˚ DEG.

MAX. LENGTH (FT.)

ELBOWS*

45

1

40

2

35

3

1 ELBOW

EXAMPLE

1 ELBOW

EXAMPLE

7

38

3. Minimum vent length for all models is 18 inches.