Locating the New Water Heater (cont’d)

9

Figure 6

Air for Ventilation for

Appliances Located in

Confined Spaces

Air for ventilation should be provided if installed in a confined
space. Refer to the National Fuel Gas Code, ANSI Z223.1.

Figure 4

WIRE FENCE

When the water heater outlet terminal is low enough to be

touched accidentally, or is accessible to small children, a

wire mesh chain link fence (as shown in Figure 6) may be

used. Care should be taken to maintain adequate ventila-

tion around the outlet terminal. If a chain link fence is

installed, it must not be used as a storage area for items that

may block proper ventilation.

NOT TO BE USED AS

A STORAGE AREA

Venting Through Roof – Clearances

0

″ clearance for 3″ PVC, ABS, or CPVC Schedule 40 piping

from combustible and noncombustible surfaces.

The vent exhaust outlet and air inlet terminals shall terminate at

least 18 inches above the roof surface. Figure 7.

The venting system must be installed in a manner which

allows inspection of the installation of the venting pipes and

joints as well as periodic inspection after installation as

required by ANSI Standards.

18

24

NATURAL DRAFT (GRAVITY)

DIRECT VENT, POWER

VENT, OR POWER DIRECT

VENT APPLIANCE INLET

AND/OR OUTLET VENT(S).

VENT OUTLET

AIR INTAKE

18

6

1

2

MIN.

24

MAX.

18

45˚

45° VENT CAP

W/SCREEN

90° STREET ELL