This water heater is equipped with an electrically operated

venting system and electronic control. For the burner to

come on, the water heater thermostat must call for heat.

Then the system will begin sequencing, each section prov-

ing itself before gas is allowed to flow to the burner.

BEFORE THE WATER HEATER WILL OPERATE:

1. The control system must be connected to a grounded

110/120 volt power supply. The control system has an

overall rating of 2 amps. The water heater must be

securely and adequately grounded in accordance with

local codes and with the current edition of the National

Electrical Code ANSI/NFPA 70.

2. The ON/OFF toggle switch, located on the control box

above the thermostat must be in the “ON” position for

the electrical control system to operate allowing the gas

portion to operate (ignite burner).

3. The venting manual reset switch must be in the closed

position. See “Venting Manual Reset Switch” in the “For

Your Information” section.

4. There is a non-resettable hi-limit switch in the thermo-

stat, which must be good (closed) for the thermostat to

be operated. See “High Temperature Shut Off System”

in the “For Your Information” section.

OPERATION

When the thermostat calls for heat, gas is allowed to flow

to a (N/O) pressure switch closing it. An electrical circuit is

then made to the blower, turning it on. When the blower

has achieved sufficient venting, the air pressure switch will

close. A 120 volt circuit will be completed through the

venting manual reset switch and on to the 120 volt gas

valve. The 120 volt gas valve will open allowing gas to

flow to the burner. The hot surface ignitor will establish a

main burner flame.

BLOWER MOTOR

AIR PRESSURE

SWITCH

VENTING HOOD

ON/OFF SWITCH

VENTING MANUAL

RESET SWITCH

BURNER

120V GAS VALVE

HOT SURFACE

IGNITOR

ALL MODELS