Omega WI8XX-U User Manual

Page 71

Advertising
background image

65

4.8.3 Device Setting and Configuration

The Meter and End Devices should first be configured and ready to use.

Make sure to have the following settings in the "Network" web page of the Meter

(Figure 4.20) .

Number of Connections = 5

Port = 2000 (other values may be acceptable as long as Mail Notifier is setup

with the same Port number)

Then on the Mail Notifier Alarm Editor, set the BusAddress/DeviceID to match

the Device ID number for an End Device and set the Reading Cmd to a

Command String from the following table:

Table 4.4 Mail Notifier Commands

Desired Value to Monitor

Reading Command Actual Command

String

String (see Note 2)

Temperature1 (Process)

SR##a

*SR05a\r

in scale configured at Meter

Temperature1 (Process)

SR##o

*SR05o\r

in Degree C

Temperature2 (Ambient at

SR##b

*SR05b\r

End Device sensor) in scale

configured at Meter

Temperature2 (Ambient at

SR##p

*SR05p\r

End Device sensor) in Degree C

Battery voltage (mV)

SR##j

*SR05j\r

Signal Level

SR##h

*SR05h\r

Success Rate

SR##i

*SR05i\r

1. The commands used in Mail Notifier are symbolic commands rather

than actual Meter commands described in Table 4.1.

2. The sample commands in the table above are shown for a sensor

with Device ID of 5 such that SR##a, for example, is sent as

*SR05a\r.