72

GENERAL

Connection:

Screw terminals

Line Voltage/Power:

90 to 240 Vac +/-10%, 50 to 400 Hz*;

110 to 375 Vdc, equivalent voltage; 5 W

* No CE compliance above 60 Hz

Low Voltage/Power Option:

20 to 36 Vdc or 24 Vac** +/-10%; 4 W

External power source must meet Safety Agency

Approvals.

** Units can be powered safely with 24 Vac power

but, no Certification for CE are claimed.

External Fuse Required:

Time-Lag, IEC 127-3 recognized:

100 mA/250 V 400 mA/250 V

(Low Voltage/Power Option)

Time-Delay, UL 248-14 listed:

100 mA/250 V 400 mA/250 V

(Low Voltage/Power Option)

Environmental Conditions:

0 to 50°C (32 to 122°F), 90% RH non-condensing

Protection:

NEMA-1/Type 1 front bezel

Dimensions:

48H x 96W x 127mm D (1.89 x 3.78 x 5")

Panel Cutout:

45H x 92mm W (1.772 x 3.622")

Weight:

353 g (0.78 lb)

Software:

The software packages available for the

Temperature Wireless System products are

iConnect (configuration software for the Ethernet

interface), iLog (Excel-based software for

automatic data logging), and Mail Notifier (email

alarm notification software).

INTERFACE SPECIFICATIONS

Ethernet:

Standards Compliance IEEE 802.3 10Base-T

(RJ45)

Supported Protocols:

TCP, UDP, ARP, ICMP, DHCP, DNS, HTTP, and

Telnet

LED Indicators:

Network Activity, Network Link, Diagnostics,

Receive & Power

Management:

Device configuration and monitoring through

embedded Web Server

Embedded Web Server:

Serves WEB pages (Java™ Applets) containing

real-time data and live updated charts within

definable time intervals.

WIRELESS COMMUNICATION

Standard:

DSSS; IEEE 802.15.4

Frequency

2.4 GHz (2410 MHz), 12 Channels

Network Topology:

Star Topology

Advertising