Part 6 specifications – Omega WI8XX-U User Manual

Page 77

Advertising
background image

71

PART 6

SPECIFICATIONS

ON/OFF CONTROL OUTPUT 1 & 2

Relay:

250 Vac or 30 Vdc @ 3 A (Resistive Load), SPDT

Solid State Relay (SSR):

20 to 265 Vac @ 0.05 to 0.5 A (Resistive Load);

continuous

DC Pulse:

Non-Isolated; 10 Vdc @ 20 mA

Analog Output (Output 1 only)

Non-Isolated, 0 to 10 Vdc or 0 to 20 mA, 500 Ω

max

Operation:

Direct (cool), reverse (heat); deadband; single

sensing input

Configuration

Output 1 and 2 can be configured as Alarm 1

and 2, respectively. Analog Output for Output 1

can be configured as retransmission.

ALARM 1 & 2 (PROGRAMMABLE)

Type:

SPDT Relay, SSR, and DC Pulse

Operation:

High/low, above/below, band, latch/unlatch,

normally open/normally closed and

process/deviation; front panel configurations;

single/multiple sensing input(s)

ANALOG RETRANSMISSION OUTPUT (PROGRAMMABLE)

Type:

Non-Isolated, Retransmission 0 to 10 Vdc or

0 to 20 mA, 500 Ω max (Output 1 only).

Operation:

Single sensing input; accuracy is + 1% of FS

when following conditions are satisfied:

1)Input is not scaled below 1% of Input FS.

2)Analog Output is not scaled below 3% of

Output FS.

INSULATION

Power to Output:

2300 Vac per 1 min. test

1500 Vac per 1 min. test

(Low Voltage/Power Option)

Power to Relays/SSR Outputs:

2300 Vac per 1 min. test

Relays/SSR to Relay/SSR Outputs: 2300 Vac per 1 min. test

GENERAL

Display:

4-digit, 9-segment LED, 10.2mm (0.40

"

) and

21mm (0.83

"

) red, green and amber

programmable colors

Digital Filter:

Programmable

Advertising