Command Descriptions

3–22

Option 01 VXI Interface Module User Manual

After this sequence, each time the VXI TTL trigger 2 is pulsed low, the
following sequence of events occurs:

1. One second delay. This is the delay specified in the trigger:Sequence:delay

command.

2. The current relay in the scan list is opened.

3. 0.5 second delay. This is the delay specified in the route:open:dwell

command.

4. Close the next relay in the scan list.

5. 0.25 second delay. This is the delay specified in the route:close:dwell

command.

6. Pulse VXI TTL trigger 1 low for 3

msec.

[ROUTe:]CLOSe:MODE <mode>,<module_name>,<section_list>

N/A

All sections of all VX4330 Modules are set to operate in the mux mode. In this
mode one or more channels in a section may be closed at the same time.

This command applies only to the VX4330 Module. The section numbers in the
<section_list> argument must be between 1 and 6.

[ROUTe:]CONFigure:JOIN
[ROUTe:]CONFigure:DISJoin
[ROUTE:]CONFigure

This command is supported only for VX4330 Modules. It sets the mode of
operation of sections on a VX4330 to scan or mux. When this command is
received, all relays in the sections specified in the <section_list> argument are
opened. In the mux mode, one or more relays in a section may be closed at the
same time. When a relay is closed in a section that has been set to scan mode, all
relays in that section are opened before the relay is closed. If several sections are
set to operate in scan mode and the commons of these sections are joined (see the
[ROUTe:]CONFigure:JOIN command) then when a relay is closed in any of the
sections, all relays in all of the sections are opened first.

Command Syntax

Query Syntax

*RST Value

Limits

Related Commands

Description