I/o interf ace – Yamaha SRCP User Manual

Page 44

Advertising
background image

3-

16

3

I/O INTERF

ACE

(2)When a command with a short execution time runs and ends normally:

(Command execution has already ended and the END signal is on before turning off
(contact open) the dedicated command input, as in the examples listed below.)

A movement command (ABS-PT, INC-PT) for a very short distance was executed.

A reset command (RESET) was executed.

A step run was executed using a command with a very short execution time such as the L and
DO statements.

Dedicated
command

30ms or less

END

BUSY

30ms or less

1ms or less

(1) At the rising edge of the dedicated command input, the END signal turns off and the BUSY

signal turns on.

(2) Turn off (contact open) the dedicated command input after checking that the BUSY signal

turns on.

(3) Wait until the BUSY signal turns off. (The BUSY signal immediately turns off since the com-

mand execution is already complete.)

(4) The END signal should be on when the BUSY signal turns off, indicating that the command

has ended normally.

However, the PRM34 (system mode selection parameter) "bit 7 END output sequence setting at
command execution completion" setting can be changed so that the END signal turns on when the
dedicated command input turns off.

n

NOTE

The PRM34 (system mode selection parameter) "bit 7 END output sequence setting at command execution
completion" setting is supported only in Ver. 24.32 and later versions.

Dedicated
command

END

BUSY

Dedicated command
execution completion

30ms or less 1ms or less

1ms or less

1ms or less

Even after dedicated command
execution completion, the END
signal does not turn on until the
dedicated command input turns
off.

3-6 I/O Control Timing Charts