6-3 when interlock signal is input, I/o interf ace – Yamaha SRCP User Manual

Page 46

Advertising
background image

3-

18

3

I/O INTERF

ACE

(4)When command execution cannot be completed:

(Command execution stops before completion and the END signal does not turn on, as
in the examples listed below.)

An interlock or emergency stop was triggered during execution of a dedicated command.

The SERVICE mode input was changed during execution of a dedicated command.

An error was caused due to a jump to an unregistered program or point during automatic
operation.

Dedicated
command

Differs according to execution command

END

BUSY

Command execution impossible

(1) At the rising edge of the dedicated command input, the END signal turns off and the BUSY

signal turns on.

(2) Turn off (contact open) the dedicated command input after checking that the BUSY signal

turns on.

(3) Wait until the BUSY signal turns off.

(4) The BUSY signal turns off since the command execution stops before completion.

(5) The END signal remains off when the BUSY signal turns off, indicating that the command

could not end normally.

3-6-3 When interlock signal is input

LOCK

BUSY

END

Interlock

Dedicated
command

Differs according to execution command

■ When a interlock signal is input while a dedicated command is being executed, the BUSY

signal turns off. The READY and END signals remain unchanged.

3-6 I/O Control Timing Charts

Advertising