3 technical data, 1 data – VEGA VEGAPULS 56V User Manual

Page 19

Advertising
background image

VEGAPULS 56V

19

3 Technical data

3.1 Data

Power supply

Supply voltage

from signal conditioning instrument VEGAMET

or processing system VEGALOG 571
(max. 36 V DC)

Fuse

0,5 A (slow-blow)

Current consumption

max. 22,5 mA

Power consumption

max. 80 mW; 0,45 VA

Load

resistance of the signal line max. 15␣

(7,5␣

with separator VEGATRENN 548V␣ Ex) per
wire or max. 1000␣ m cable length

Measuring range

1)

Standard

0 … 20 m

Measurement in standpipe
- VEGAPULS 56 on DN 50

0 … 16 m

- VEGAPULS 56 on DN 100

0 … 19 m

Output signal

(see also "Outputs and processing“)

Digital measuring signal (VBUS)

Adjustment

- PC and adjustment software VEGA Visual Operating
- adjustment module MINICOM
- signal conditioning instrument VEGAMET (6-key-adjustment field on signal conditioning

instrument)

Accuracy

(typical values under reference conditions)

2)

Class accuracy

< 0,1 % (deviation in characteristics including

repeatability and hysteresis according to the
limit point adjustment relating to max.
measuring range)

Linearity error

better than 0,05 %

Influence
- of the ambient temperature

2)

0,06 %/10 K

- of the process temperature

2)

negligible (0,004 %/10 K at 5 bar)
(0,003 %/10 K at 40 bar)

- of the process pressure

0,025 %/bar

Resolution of the digital output signal

0,005 % (relating to max. measuring range)

Adjustment time

1 … 10 s (dependent on factory setting)

Resolution

1 mm

Technical data

1)

Min. distance of the antenna tip to the medium 5 cm

2)

Reference conditions according to IEC 770