Construction instructions for standpipe, Mounting and installation – VEGA VEGAPULS 56V User Manual

Page 38

Advertising
background image

38

VEGAPULS 56V

0 %

~45

••

ø 51,2

0,0…0,4

1,5…2

2,9

0,0...0,4

150…500

5…15

2,9…6

100 %

Mounting and installation

Construction instructions for standpipe

Radar sensors for measurement on surge or
bypass pipes are used in flange sizes
DN!50, DN!80, DN!100 and DN!150.

On the left is the construction of a measuring
pipe (surge or bypass pipe) in the example
of a sensor with a DN!50 flange.

The radar sensor with a DN!50 flange is only
in conjunction with a measuring pipe a func-
tional system.

The measuring pipe must be smooth inside
(average roughness Rz!

≤!30). Use as mea-

suring pipe a stainless steel pipe without
joint. Extend the measuring pipe to the re-
quired length with welding neck flanges or
with connecting sleeves. Note that no shoul-
ders are caused in the pipe during welding.
Fasten the pipe and the flange before weld-
ing in alinement with the inner sides.

Do not just weld through the pipe wall.
Roughnesses or joints must be removed
carefully as otherwise strong false echoes
and build-up will be caused.

Flange DN 50

Welding neck flange

Connecting
sleeve

Welding neck
flanges

Welding of the connect-
ing sleeve

Welding of the welding
neck flange

Fastening of
measuring pipe

Vessel bottom

Deflector

Min. product level
to be measured
(0!%)

Rz

≤ 30

Burr the
holes