2 measurement of liquids, Heat isolation, Sensor on din-socket piece – VEGA VEGAPULS 56V User Manual

Page 32: Mounting and installation

Advertising
background image

32

VEGAPULS 56V

0

2,4 m

3,8 m

2,4 m

3,8 m

10 m

0 m

20 m

14

••

22

••

50 %

100 %

Heat isolation

Mounting on a longer DIN-socket piece

>!10!mm

Emission cone of a DN 250 horn antenna

Measuring
distance

Mounting and installation

Heat isolation

In case of process temperatures of more
than 200

°C an isolation on the rear of the

flange is necessary to separate the radiation
heat from the sensor electronics.

The best would be to include the sensor
isolation into the vessel isolation and isolate it
up to approx. the first pipe segment.

4.2 Measurement of liquids

Sensor on DIN-socket piece

Most of the time the mounting of radar sen-
sors is made on short DIN-socket pieces.
The instrument flange is the reference plane
of the measuring range. The antenna should
always protrude out of the flange pipe.

Mounting on short DIN-socket piece

Reference plane

When the DIN-socket piece is longer, note
that the horn antenna must protrude at least
10 mm out of the socket.

When mounting on dished end vessels the
antenna has to protrude at least 10 mm.

40

°C

60

°C

100

°C 240°C

350

°C

Vessel isolation

max. 350

°C

Emitted power

Emitted power