VEGA VEGAPULS 56V User Manual

Page 50

Advertising
background image

50

VEGAPULS 56V

• Click in the menu window "

Create new

measurement loop - Measurement loop
designation“ to "Level“.

Set-up

• Choose "Standard level measurement“ and

"No options“.

• Click to "Continue“ and the menu window

"

New application - select meas. loop“

opens.

• Choose one of the two inputs of the signal

conditioning instrument VEGAMET (VEGA-
MET 514V has only one sensor input) and
click to "OK“.

After a few seconds the menu window "

Cre-

ate new measurement loop - Sensor configu-
ration“ opens.

• Click in the menu window "

Create new

measurement loop - Sensor configuration“
to "Sensor coordination“.

The menu window "Sensor coordination
opens.

• Click to "Sensor search“.
• Then click to "Input“ and choose the serial

number of the sensor which you want to
coordinate e.g. to input 1.

• Confirm with "OK“.
• Click in the menu window "

Sensor coordi-

nation“ again to "OK“.

You are again in the menu window "

Create

new measurement loop - Sensor configura-
tion“

• Click to "Continue“.