1a configuration measurement loop, 1b configuration input, 2) measurement in standpipe – VEGA VEGAPULS 56V User Manual

Page 63: 3 adjustment

Advertising
background image

VEGAPULS 56V

63

Max.

Min.

100 % (0,500 m) corresp. to
1200 liters

Meas. range

0 % (3,400 m) corresp. to
45!liters

Set-up

Adjust-
ment

Pa-
ram-
eter
adjust-
ment

Sensor

m(d)

4.700

without
medium

Ad-
just-
ment
in

m(d)

0.0 %

at

m (d)

XX.XXX

(Min-adjustment)

OK

OK

+

OK

OK

1a Configuration measurement loop

(menu plan page 68)

1b Configuration input

First of all you have to inform the signal condi-
tioning instrument (only VEGAMET 515V) to
which input (input 1 or input 2) the sensor is
connected. Proceed according to chapter
"6.1 Configuration measurement loop“ in the
operating instruction VEGAMET 515V (menu
plan page 68).

2) Measurement in standpipe

Adjustments are only required when the
sensor is mounted to a standpipe. With the
measurement in a standpipe the running time
of the radar signal changes which is depen-
dent on the inner resistance of the standpipe.
Enter the distance from the sensor flange to
the medium. Then the sensor calculates a
precise running time correction and provides
exact level values (menu plan page 72).

3 Adjustment

Under the menu point "

Adjustment“ you in-

form the sensor in which measuring range it
should operate. You can carry out the adjust-
ment with or without medium. Generally you
will carry out the adjustment without medium
as you can adjust without filling cycle.

Adjustment without medium
Input (key)

Display indication

OK

100.0%

at

m (d)

XX.XXX

The distance indication flashes
slowly

Now you can adjust with the "

+“ and "–“-key

the distance of your sensor to the medium at
0 %-filling (example: 3,400 m).

The indication stops flashing
and the adjustment will be
saved.

Hence you have adjusted to min. value.

(Max-adjustment)

Proceed with the 100!%-value, where you
enter e.g. 0,500!m.