Again in the menu window "

Conditioning“ you

can enter with the menu point "

Integration

time“ a measured value integration. This is
useful for fluctuating product surfaces to
avoid a permanently varying measured value
indication and output.
As a standard feature an integration time of 0
seconds is adjusted.

• Quit the menu window "

Integration time“

with "OK“ and you are again in the menu
window "

Conditioning“.

• Quit the menu window with "Quit“.

You are again in the menu window "

Instru-

ment data parameter adjustment“.

• Click to "Quit“.

Outputs

• Choose in the main menu window "Instru-

ment data/Parameter adjustment“ and in
the following window the requested sensor.

• Choose in the menu window "

Instrument

data parameter adjustment“ "Outputs“.

Set-up

• Click to "Show scaled values“, to have the

adjusted unit displayed on the y-axis (left
bottom corner in the menu window).

Index marker 0 is at 0 %-filling (percentage
value [%]), corresponding to an actual dis-
tance to the product surface of 3,400 m, in
the example the empty vessel. The volume
value is therefore 45 liters (rest filling of the
vessel).

Index marker 1 is at a level of 20 % (20 % of
the measuring distance of 0,500␣ m␣ …␣ 3,400␣ m).
According to our example there are 100 liters
at 20 % filling in the vessel.

Index marker 2 is at a level of 40 %. At this
filling level there are 250 liters in the vessel.
Index marker 3 is at a level of 80 %, where
1000 liters are in the vessel.
Index marker 4 is at a level of 100 % (prod-
uct distance 0,500 m), where 1200 liters are
in the vessel.

Max. 32 index markers (values pairs) can be
entered per linearisation curve.

• Quit the menu with "OK“.
• Confirm the message with "OK“ and your

individual linearisation curve is saved in the
sensor.