3 input/output state, 4 set/run – SENA Rhio10 User Manual

Page 54

Advertising
background image

54

5.3.3 Input/Output State

5.3.3.1 I/O State Request Command

Command

Data

Remark

Byte Size

2

1

“03”

( 0x30, 0x33 )

State Request

0x30: Fixed to a

dummy value

5.3.3.2 Response for I/O State Request Command

-

Identical with ON/OFF control response.

-

Sent even if the state of input port or ADC (in Switch Input mode) has been changed

(based on a threshold voltage). A change of input state is recognized when the input

value changed is maintained for 15 ms.

-

In case of state response, the control state field returns 0x30 in Run mode and 0x31 in

Setting mode.

5.3.4 Set/Run

5.3.4.1 Set/Run Command

Command

Data

Remark

Byte Size

2

1

“04”

( 0x30, 0x34 )

Set/Run

0x30: Set

0x31: Run

Switch between Set

and Run Modes.

-

Rhio10 returns a state response once after set command is received. It does not return

any state response until it receives run command even if it is switched to Setting mode.

-

When setting output port, ADC input port, Port Enable, Port Power-out Recovery or

serial number, send set command first to switch it to Setting mode. (Check command is

working in both Setting and Run mode.)

-

Once each setting is completed, send run command to switch it to Run mode.

-

When a run command is received, it returns a state response once and continues with

the operation paused.