1.3 Product Specification

10 Base-T Ethernet with RJ45 Ethernet connector

Network Interface

Supports static and dynamic IP address

Digital Input

-Number of channels: 12

-Input type: Voltage

-Input circuitry: Optically isolated photo-coupler

-Input range: 0V ∼ ±24V

OFF 0V ∼ ±1.2V, ON ±3.3V ∼ ±24V

-Sampling rate: 20ms

-Isolation voltage: 5KV

Digital Output

- Number of channels: 10

- Output type: Relay

- Rated load: 3A/240VAC

- Insulation resistance: 1000㏁ Min (DC500V)

- Isolation voltage(coil and contact): 4KV

- Reaction within 10ms

Analog Input

- Number of channels: 4

- Effective resolution: 10-bit

- Input type: Voltage, Direct Coupling

- Input range: 0V ∼ Aref (Analog reference voltage, 2~5V)

- Sampling rate: 1000 samples/sec

Protocol

ARP, IP/ICMP, TCP

telnet, DHCP client, PPPoE

Management

- Rhio Manager Windows Utility, Serial Console or Telnet

Software Support

- Windows MFC DLL library

- I/O configuration, I/O status monitoring/control

Diagnostic LED

- Power, Link, Act

- Digital Output, 1~10

- Digital Input, 1~12

- Analog Input, 1~4

Power

9V∼48VDC, Max. 5W

Environmental

- Operating temperature: 0℃ to 50℃

- Storage temperature: -20℃ to 66℃

- 90% Non-condensing