3.1.3 LED Behaviour

The option has 3 bi-coloured LEDs according to ODVA specifications:

LED Label

Description

MS

Module Status

NS1

Network Status Ethernet Port 1

NS2

Network Status Ethernet Port 2

The option LED’s operates according to ODVA specifications.

State

LED

Description

No power

Off

The device is un-powered

Device operational

Green:

Solid green

The device is operational

Standby

Green:

Flashing green

The device needs commissioning

Minor fault

Red:

Flashing red

The device has detected a recoverable fault

Major fault

Red:

Solid red

The device has detected an un-recoverable fault

Self test

Red:

Flashing red/green The Modbus TCP option is in self-test mode

Green:

No IP address

Yellow

Steady yellow

No IP address configured or obtained

Wink

Yellow

Flashing yellow

Flash for 20 seconds

Table 3.1: MS: Module Status

State

LED

Description

No IP-address (no power)

Off

No link present (or is un-powered)

Connected

Green:

Solid green

There is established (at least) one CIP connection to
the device

Duplicate IP

Red:

Solid red

The IP-address assigned to the device is already in
use

Self test

Red:

Flashing red/green The Modbus TCP is in self-test mode

Green

Device has been winked

Yellow

Flashing yellow

Flash for 20 seconds

Link present at 10 Mbps

Yellow

Steady yellow

Link present; but nor winked and no ACD

Table 3.2: NS1 + NS2: Network Status (one per port)

Modbus TCP

9