Modbus tcp – GE Industrial Solutions AF-600 FP OPCMBTCP Modbus TCP Option User Manual

Page 39

Advertising
background image

EN-04 DHCP Server

Range:

Function:

[000.000.000.000 – 255.255.255.255] Read only. Displays the IP address of the found DHCP or BOOTP server.

NB!
A power-cycle is necessary after setting the IP parameters manually.

EN-05 Lease Expires

Range:

Function:

[dd:hh:mm:ss]

Read only. Displays the lease-time left for the current DHCP-assigned IP address.

EN-06 Name Servers

Option:

Function:

IP addresses of Domain Name Servers. Can be automatically assigned when using DHCP.

[0]

Primary DNS

[1]

Secondary DNS

EN-07 Domain Name

Range:

Function:

Blank

[0-19 characters]

Domain name of the attached network. Can be automatically assigned when using DHCP.

EN-08 Host Name

Range:

Function:

Blank

[0-19 characters]

Logical (given) name of option.

EN-09 Physical Address

Range:

Function:

[00:1B:08:00:00:00 – 00:1B:
08:FF:FF:FF]

Read only Displays the Physical (MAC) address of the option.

EN-1# Ethernet Link Parameters

Option:

Function:

Applies for whole parameter group.

[0]

Port 1

[1]

Port 2

EN-10 Link Status

Option:

Function:

Read only. Displays the link status of the Ethernet ports.

[0]

No link

[1]

Link

EN-11 Link Duration

Option:

Function:

Link Duration Port 1 (dd:hh:mm:ss)

Read only. Displays the duration of the present link on each port in dd:hh:mm:ss.

EN-12 Auto Negotiation

Option:

Function:

Configures Auto Negotiation of Ethernet link parameters, for each port: ON or OFF.

[0]

Off

Link Speed and Link Duplex can be configured in par. EN-13 and EN-14.

[1]

On

Modbus TCP