Check: LEDs
The option contains two LEDs to indicate the state of the device and the network. During normal operation the MS and at least one NS LED will show a constant
green light.

State

LED

Description

No power

Off

The device is un-powered

Device operational

Green:

Solid green

The device is operational

Standby

Green:

Flashing green

The device needs commissioning

Minor fault

Red:

Flashing red

The device has detected a recoverable fault

Major fault

Red:

Solid red

The device has detected an un-recoverable fault

Self test

Red:

Flashing red/green The Modbus TCP option is in self-test mode

Green:

No IP address

Yellow

Steady yellow

No IP address configured or obtained

Wink

Yellow

Flashing yellow

Flash for 20 seconds

Table 7.1: MS: Module Status

State

LED

Description

No IP-address (no power)

Off

No link present (or is un-powered)

Connected

Green:

Solid green

There is established (at least) one CIP connection to
the device

Duplicate IP

Red:

Solid red

The IP-address assigned to the device is already in
use

Self test

Red:

Flashing red/green The Modbus TCP option is in self-test mode

Green

Device has been winked

Yellow

Flashing yellow

Flash for 20 seconds

Link present at 10 Mbps

Yellow

Steady yellow

Link present; but nor winked and no ACD

Table 7.2: NS1 + NS2: Network Status (one per port)

Check: Link Status
The status of the Ethernet link cannot be directly identified by means of the LEDs.
Use par. EN-10, Link Status to verify presents of the link.
Use par. EN-11, Link Duration to verify that the link is steady present.
The parameter will show the duration of the present link, and preset to 00:00:00:00 if the link is broken.

Check: Cabling
In rare cases of cabling mis-configuration, the option might show the presents of a link, but no communication is running. Exchange the cable in doubt.

Check: IP Address
Verify that the option has a valid IP address (please refer to section: IP Settings) in par. EN-01, IP Address. If the option has identified a duplicate IP Address NS
LEDs will light steady red. If the option is set up for BOOTP or DHCP, verify that a BOOTP or DHCP server is connected in par. EN-04, DHCP Server. If no server is
connected, the parameter will show: 000.000.000.000.