Modbus tcp, 4 holding register addressing – GE Industrial Solutions AF-600 FP OPCMBTCP Modbus TCP Option User Manual

Page 25

Advertising
background image

5.2.4 Holding Register Addressing

Holding registers

Register Number

Description

00001-00006

Reserved

00007

Last error code from an Drive data object interface

00008

Reserved

00009

Parameter index*

00100-00999

000 parameter group (parameters 001 through 099)

01000-01999

100 parameter group (parameters 100 through 199)

02000-02999

200 parameter group (parameters 200 through 299)

03000-03999

300 parameter group (parameters 300 through 399)

04000-04999

400 parameter group (parameters 400 through 499)

...

...

49000-49999

4900 parameter group (parameters 4900 through 4999)

2810

Input data: Frequency converter control word register (CTW).

2811

Input data: Bus reference register (REF).

...

...

2910

Output data: Frequency converter status word register (STW).

2911

Output data: Frequency converter main actual value register (MAV).

* Used to specify the index number to be used when accessing an indexed parameter.