5.4 GE Drive Control Profile

5.4.1 GE Drive Control Profile

Illustration 5.1: (par. O-10 Control Word Profile = Drive profile)

Bit

Bit value = 0

Bit value = 1

00

Reference value

External selection LSB

01

Reference value

External selection MSB

02

DC brake

Ramp

03

Coasting

No coasting

04

Quick stop

Ramp

05

Hold output frequency

Use ramp

06

Ramp stop

Start

07

No function

Reset

08

No function

Jog

09

Ramp 1

Ramp 2

10

Data invalid

Data valid

11

No function

Relay 01 active

12

No function

Relay 04 active

13

Parameter set-up

Selection LSB

14

Parameter set-up

Selection MSB

15

No function

Reverse

Explanation of Control Bits
Bits 00/01
Bits 00 and 01 are used to choose between the four reference values, which
are pre-programmed in par. C-05 Multi-step Frequency 1 - 8 according to the
following table:

Programmed

ref. value

Parameter

Bit 01

Bit 00

1

C-05 [0]

0

0

2

C-05 [1]

0

1

3

C-05 [2]

1

0

4

C-05 [3]

1

1

NB!
In par. O-56 Preset Reference Select select a selection is made to define how
Bit 00/01 gates with the corresponding function on the digital inputs.

Bit 02, DC brake:
Bit 02 = ‘0’ leads to DC braking and stop. Braking current and duration are set
in par. B-01 DC Brake Current and par. B-02 DC Braking Time. Bit 02 = ‘1’ leads
to ramping, par. F-07 Accel Time 1

Bit 03, Coasting:
Bit 03 = ‘0’ causes the frequency converter to immediately "let go" of the motor
(the output transistors are "shut off"), so that it coasts to a standstill.
Bit 03 = ‘1’ enables the frequency converter to start the motor if the other
starting conditions have been fulfilled.

NB!
In par. O-50 Coasting Select a selection is made to define how Bit 03 gates
with the corresponding function on a digital input.

Bit 04, Quick stop:
Bit 04 = ‘0’ causes a stop, in which the motor speed is deceled to stop via
par. C-23 Quick Stop Decel Time.

Bit 05, Hold output frequency:
Bit 05 = ‘0’ causes the present output frequency (in Hz) to freeze. The frozen
output frequency can then be changed only by means of the digital inputs
(par. E-01 Terminal 18 Digital Input to par. E-06 Terminal 33 Digital Input) pro-
grammed to Speed up and Speed down.

NB!
If Freeze output is active, the frequency converter can only be stopped by
the following:

Bit 03 Coasting stop

Bit 02 DC braking

Digital input (par. E-01 Terminal 18 Digital Input to par. E-06 Ter-
minal 33 Digital Input
) programmed to DC braking, Coasting stop
or Reset and coasting stop

Modbus TCP

28