Modbus tcp – GE Industrial Solutions AF-600 FP OPCMBTCP Modbus TCP Option User Manual

Page 21

Advertising
background image

By first selecting the GE network and secondly selecting the IO Scanning tab, the scanning list appears. You will have to fill out the list as shown here

Menu

Menu point

Setting

IO Scanning

IP address

192.168.001.030

Unit ID

255

Health Timeout

1500

Repetitive rate

60

RD Master Object

%MW100

RD Slave Index

50009

RD Length

10

Last Value

Hold Last

VR Master Object

%MW200

VR Slave Index

0

VR Lenght

10

Description

-

This configuration copies the information stored from %MW200 to %M209 in the PLC to the Holding register 50010 to 500019 of the AF-650 GP. It reads the holding
registers 50000 to 50009 of the AF-650 GP to the PLC’s memory %MW100 to %M109

Modbus TCP