6.2.1 Modbus TCP

EN-40 MODBUS TCP Status

Range:

Function:

[0]

[1]

Read only. Displays the Modbus TCP- specific 16-bit Status word.

Bit

Description

Bit = [0]

Bit =[1]

0

Link Status port
1

Disconnected

Connected

1

Link Status port
2

Disconnected

Connected

2

Link speed

0/10 Mbps

100 Mbps

3

Link Duplex

Half

Full

4

Port 502 com-
munication

No

Yes

5

UNUSED

-

-

6

Valid IP address No

Yes

7

Modbus time-
out (30 s)

No

Yes

8

Duplicate IP

No

Yes

9

Register 7 error No

Yes

10

FTP server

Disabled

Enabled

11

HTTP server

Disabled

Enabled

12

SMTP service

Disabled

Enabled

13

Cable diagnosis Disabled

Enabled

14

Auto crossover Disabled

Enabled

15

IGMP snooping Disabled

Enabled

EN-41 Slave Message Count

Option:

Function:

Read only.
Displays the number of Modbus messages received and processed by the slave.

EN-42 Slave Exception

Option:

Function:

Read only.
Displays the number of Modbus messages for which the slave has sent an exception response.

EN-80 FTP Server

Option:

Function:

[0] *

Disable

Disables the built-in FTP server.

[1]

Enable

Enables the built-in FTP server.

EN-81 HTTP Server

Option:

Function:

[0] *

Disable

Disables the build-in HTTP (web) server.

[1]

Enable

Enables the build-in HTTP (web) server.

Modbus TCP

40

6