3.1.2 How to Install Option in Frequency Converter

Items required for installing a network option in the frequency converter:

-

The network option

-

Network option adaptor frame for the AF-650 GP/AF-600 FP. This frame is deeper than the standard frame, to allow space for the network option beneath

-

Strain relief (only for unit size 12)

Instructions:

-

Remove Keypad panel from the AF-650 GP/AF-600 FP.

-

Remove the frame located beneath and discard it.

-

Push the option into place. The Ethernet connectors must be facing upwards.

-

Remove both knock-outs on the network option adaptor frame.

-

Push the network option adaptor frame for the AF-650 GP/AF-600 FP into place.

-

Replace the Keypad and attach cable

NB!
Do not strip the Ethernet cable and ground it via the strain relief-plate! The grounding of screened Ethernet cable is done through the RJ-45 connector on the
option.

NB!
After installing the OPCMBTCP option, be aware of the following parameter settings:
par. O-01 Control Site: [2] Controlword only or [0] Digital and ctrl. word
par. O-02 Control Word Source: [3] Option A

Modbus TCP